Add Up the Exhaust in a Modern House. Then Find Where the Air Comes Back.

A door that pulls hard against you when the range hood is running. A gas fireplace that smells faintly when somebody is in the shower with the bath fan on. A cold draft that only shows up when the dryer is going.

Three different complaints, three different rooms, and the homeowner describes each one as its own problem. They are the same problem.

Air is leaving the building and the building is finding its own way to replace it.

Do the Arithmetic

Walk a current build and count what moves air out of it.

Range hood. Dryer. A bath fan in every bathroom. Often a second one. Powered downdraft on the cooktop in nicer kitchens. HRV or ERV exhaust side. Sometimes a central vacuum that exhausts outdoors.

Read the nameplates and add them up rather than estimating. The total is almost always bigger than people expect, and it has gone up substantially in the last twenty years. Kitchen exhaust in particular has grown a lot, because open plan kitchens with gas cooktops need it and the market responded.

Now count what is designed to bring air back in. In most houses the honest answer is nothing, or one passive opening sized for the furnace and nothing else.

That gap is the whole issue.

The Envelope Used to Handle This

It worked fine for decades because houses leaked.

A house built in 1975 had gaps at the rim joist, windows that were not sealed well, penetrations nobody taped, and an attic hatch that breathed. Run a fan and air came back in through the building itself, distributed across a hundred small openings. Nobody had to design for it because the construction did it accidentally.

Current construction does not leak. Vapour barrier, spray foam, sealed penetrations, better windows, blower door testing on anything to a performance standard. That is all an improvement and nobody is arguing otherwise.

But it removed the thing that was quietly supplying replacement air, and in a lot of cases nothing replaced it.

So Where Does It Come From

Whatever opening offers the least resistance.

In a tight house with no designed inlet, the openings left are appliance vents. A flue, a chimney, an atmospherically vented water heater, a combustion air intake. Those are purpose built holes to the outdoors with smooth pipe and no restriction, and they are the easiest path available.

Which means the replacement air comes down a vent. Combustion products that should be going out come back in with it. That is backdrafting, and the only thing standing between it and an actual carbon monoxide event is how long the fan runs and what appliance is firing at the time.

Worth noting that the equipment does not have to be faulty for this to happen. Everything can be installed correctly, vented correctly, and working exactly as designed. The building is just losing a pressure contest it was never set up to win.

Why the Symptoms Do Not Look Like a Safety Problem

This is the part that makes it hard to catch.

Depressurization presents as comfort and nuisance complaints. A door that sticks. A whistle around a window. A room that feels drafty when a particular fan runs. A fireplace that smells. None of those sound like a combustion problem and none of them get reported as one.

They get reported separately, usually to different people, often months apart. The door is a carpentry complaint. The draft is an insulation complaint. The fireplace smell is a fireplace complaint. Nobody connects them because nobody is looking at the house as a pressure system.

If you are in a house and two or three of those are present, it is worth asking what runs when the symptom shows up. The answer is usually a fan.

Giving It a Designed Path

The fix is a controlled opening that brings air back in when air is going out, and seals the rest of the time.

It has to close when nothing is running. A permanently open duct to the outdoors is a heating penalty every hour of the season and it creates its own comfort complaints, which is why passive openings get blocked off by homeowners and why that keeps happening.

So it is a motorized damper in a make up air duct, interlocked to whatever is causing the exhaust. Fan runs, damper opens, air comes in through the duct you chose rather than through the flue. Fan stops, damper closes, building seals back up.

On a 120 Vac exhaust fan the ADP-1101-05A handles that interlock, taking the fan circuit as its signal. More detail in the make up air post.

Make Up Air Is Not Combustion Air

These get treated as the same thing on job sites and they are not.

Combustion air feeds a specific appliance, is sized to that appliance, and on a motorized intake the appliance cannot fire until the damper proves open. Make up air replaces what an exhaust fan removes and is sized to the exhaust rate.

A house with a serious range hood and an atmospherically vented appliance needs both, serving different things. Installing one does not cover the other. The comparison post works through where each belongs.

On an Existing House

Three things worth checking when the symptoms are there.

What runs when it happens. Get the homeowner to narrow it down. The complaint is usually tied to one specific fan and they already know which, they just have not connected it.

Whether there is any designed inlet at all. Often there is a combustion air duct for the furnace and that is it, which means the range hood and the dryer and the bath fans are all drawing against a building with one small opening sized for something else.

Whether the inlet that exists is actually open. A passive hood that has drifted shut or a screen packed with debris is the same as having no inlet. That is a separate post but it compounds this one.

A retrofit make up air duct with a motorized damper is not a small job, but it is a known job, and on a house with a backdraft symptom it is the only thing that actually addresses the cause rather than the complaint.

On New Construction

Easier, and it is a design decision rather than a repair.

Total the exhaust at design. Decide what is supplying the replacement air. Put the make up air duct and its damper on the drawings with the interlock specified by model number, the same way the combustion air damper is.

Leaving it out does not mean the house does not get make up air. It means the house gets it from the flue.

If you are working through sizing or the interlock on a specific building, call 1-800-661-7382.

View motorized dampers and relay adaptors

Related: combustion air, fresh air and make up air are three different systems