Honeywell Cross-Reference

Replacing a Honeywell ARD9TZ

The Hoyme HAC-0910-OPC replaces the Honeywell ARD9TZ 9 in. round zone damper. It fits the same 9 in. round duct, runs on the same 24 Vac, and works the same way: power drives it closed, and a spring opens it when power is removed. 9 in. is the largest size on the Hoyme spring motor.

Buy the HAC-0910-OPCFind a wholesaler

Side by side

ARD9TZ and HAC-0910-OPC

Honeywell figures are from Resideo's published literature. The HAC is CSA certified for Canada and the USA.

Honeywell ARD9TZ vs. Hoyme HAC-0910-OPC
Spec Honeywell ARD9TZ Hoyme HAC-0910-OPC
Type Zone damper, round, normally open Motorized inline air damper, round
Duct size 9 in. 9 in.
Action Power close, spring open Power close (PC), spring open
Supply 24 Vac 24 Vac
Open signal LED on the optional M4 wire End switch version, HAC-0910-SPC
Service parts Replacement actuator, M847D-ZONE Field-replaceable motor, microswitch and spring kits

Sources: Resideo ARD and EARD Series Damper submittal sheet and M847D actuator specifications; Hoyme HAC product information.

Controls and wiring

Will it work with what is already there?

The ARD9TZ and the HAC-0910-OPC both power closed on 24 Vac and spring open when power is removed, so a zone panel that drove the ARD9TZ drives the HAC the same way.

Zone panels limit how much damper load each zone output can carry. On a Honeywell TrueZONE HZ322, for example, Resideo budgets each ARD at 8 VA against a limit of 28.8 VA per zone at 100°F (38°C). If the zone you are working on is already close to its limit, call technical support to confirm the load before adding dampers.

Check the old actuator first. An ARD can be field-converted to power open by fitting an M847D-VENT actuator. If the actuator on the old ARD9TZ is an M847D-VENT, order the power open version, HAC-0910-OPO, instead.

Before you order

Four checks before you swap it

  • Confirm the size. The number in the model is the duct diameter, so the ARD9TZ is 9 in. If the label reads ARD9TZ/U, it is the same damper; /U is a packaging suffix.
  • Keep the action. An ARD9TZ as shipped is power close, so order the -OPC ending.
  • Check how the old damper closed. ARD range stops can be set to bleed some air through a closed zone. A standard HAC closes fully. On a single-speed furnace, the HAC-0910-OPC-H has a fixed 10% bypass machined into the blade.
  • Panel needs a proving or relay output? Order HAC-0910-SPC for an end switch or HAC-0911-OPC for a relay.

Order options

Hoyme part numbers in 9 in.

9 in. power close options
Part number Version Use it for
HAC-0910-OPC Standard Most replacements
HAC-0910-OPC-H 10% heat bypass Supply zones on a single-speed furnace
HAC-0910-SPC End switch Panels or interlocks that wait for the blade to open
HAC-0911-OPC Relay A switched output when the damper opens

Hoyme dampers are sold through HVAC wholesalers across Canada, or you can order direct here. See how to buy.

More replacements

Other Honeywell models

Equivalent means the Hoyme damper matches the Honeywell damper's duct size, action and supply voltage. The two are not identical in construction, performance, listing or certification. Confirm the application, the control sequence and the requirements of the authority having jurisdiction before substituting any product. Honeywell Home and TrueZONE are trademarks of Honeywell International Inc., used under license by Resideo Technologies, Inc. Hoyme Manufacturing Inc. is not affiliated with, endorsed by or sponsored by Honeywell or Resideo. Model numbers are used only to identify the product being replaced. Honeywell specifications are taken from published Resideo literature as of November 2026 and are subject to change.

Not sure which version you need?

Call with the old model number and what the damper connects to. We will confirm the size, the action and the interlock before you order. Free for contractors, installers and wholesalers.

1-800-661-7382