HAC-44
Belimo TFB120
Inline Damper
100–240 Vac · Spring Return · 6"–20" · No Transformer Required
Modulating 2–10 VDC → HAC-43
Floating point, line voltage → HAC-35
Fire & smoke at 120 Vac → HAC-80
What It Does
On/off spring return inline damper control at line voltage — no transformer, no low-voltage circuit required.
The HAC-44 is the line-voltage companion to the HAC-40 (TFB24). Same Hoyme inline damper body. Same on/off spring return behavior. Same PO/PC configuration options. Same 6"–20" size range. The single difference: the Belimo TFB120 actuator accepts 100–240 Vac directly, eliminating the need for a step-down transformer or a separate low-voltage control circuit.
Where line voltage is what's already at the damper location — commercial RTU fresh air intakes controlled from line-voltage RTU panels, industrial make-up air controlled by line-voltage contactors, retrofit installations where adding 24 Vac infrastructure is impractical — run the switched line-voltage circuit directly to the actuator. No transformer. No extra wiring run.
TFB120 vs. TFB24 — Voltage Is the Only Meaningful Difference
Use the voltage that's already at the damper location. The choice is a site condition, not a product upgrade decision.
| Spec | HAC-40 (Belimo TFB24) | HAC-44 (Belimo TFB120) — this product |
|---|---|---|
| Supply Voltage | 24 Vac or 24 Vdc | 100–240 Vac (line voltage) |
| Control Type | On/Off spring return | On/Off spring return |
| Fail-Safe | Spring return on power loss | Spring return on power loss |
| PO / PC | Both available | Both available |
| End Switch | Optional | Optional |
| Relay Option | Available | Not available on TFB120 |
| Heat Bypass (−H) | Available | Available |
| CSA Status | Certified to 12" | Confirm with Hoyme before ordering |
| Sizes | 6"–20" | 6"–20" |
| Use When | 24 Vac/dc control available | Line voltage only at damper location |
Belimo Series — Control Type Selector
All Belimo-actuated HAC variants on a single Hoyme inline damper body. Select by control type and voltage.
| Model | Actuator | Control Type | Voltage | Spring Return | Link |
|---|---|---|---|---|---|
| HAC-40 | TFB24 | On/Off | 24 Vac/dc | Yes | View |
| HAC-44 ← You are here | TFB120 | On/Off | 100–240 Vac | Yes | — |
| HAC-43 | TFB24-SR-T | Modulating 2–10 VDC | 24 Vac/dc | Yes | View |
| HAC-60 | LMB24-SR-T | Modulating 2–10 VDC | 24 Vac/dc | No — holds last | View |
| HAC-34 | CMB24-3-T | Floating point 3-wire | 24 Vac/dc | No — holds last | View |
| HAC-30 | LMB24-3-T | Floating point 3-wire | 24 Vac/dc | No — holds last | View |
| HAC-35 | CMB120-3 | Floating point 3-wire | 100–230 Vac | No — holds last | View |
| HAC-70 | LMX120-3 | Floating point 3-wire | 100–230 Vac | No — holds last | View |
| HAC-90 | FSLF24 US | Fire & Smoke (UL 555S) | 24 Vac | Yes | View |
| HAC-80 | FSLF120 US | Fire & Smoke (UL 555S) | 120 Vac | Yes | View |
Configuration Guide
Select size, action, end switch, and heat bypass. PO/PC cannot be changed after installation — confirm before ordering.
| Variant Code | Action | Heat Bypass | End Switch | Part Number Example (10") |
|---|---|---|---|---|
| OPO | Power Open | No bypass | No | HAC-1044-OPO |
| OPO-H | Power Open | 10% bypass | No | HAC-1044-OPO-H |
| SPO | Power Open | No bypass | Yes | HAC-1044-SPO |
| SPO-H | Power Open | 10% bypass | Yes | HAC-1044-SPO-H |
| OPC | Power Close | No bypass | No | HAC-1044-OPC |
| OPC-H | Power Close | 10% bypass | No | HAC-1044-OPC-H |
| SPC | Power Close | No bypass | Yes | HAC-1044-SPC |
| SPC-H | Power Close | 10% bypass | Yes | HAC-1044-SPC-H |
PO vs. PC — Which Action for Your Application
| Action | When Signal Applied | Fail-Safe on Power Loss | Typical Application |
|---|---|---|---|
| PO — Power Open | Damper opens | Spring-closes — duct seals | Fresh air intake, make-up air — standard |
| PC — Power Close | Damper closes | Spring-opens — duct stays open | Applications requiring fail-open on power loss |
Key Specs
Common Questions from the Counter
Answers to what comes up most when specifying the HAC-44.