HAC-80
Belimo FSLF120 US
Fire & Smoke Damper
UL 555S Listed Actuator · Spring Return · 120 Vac · 6"–20"
No UL 555S listing required → use HAC-44 (TFB120) for line-voltage on/off at significantly lower cost.
What It Does
UL 555S listed smoke damper actuator. 120 Vac. Line-voltage companion to the HAC-90 (FSLF24 US).
The HAC-80 pairs Hoyme's inline damper body with the Belimo FSLF120 US — the 120 Vac version of the FSLF fire and smoke actuator series. Same UL 555S listing as the FSLF24 US used in the HAC-90. Same smoke damper application requirements. Same elevated temperature construction and UL 555S torque and actuation speed requirements. The single difference from the HAC-90 is supply voltage: the FSLF120 US accepts 120 Vac directly, eliminating the need for a step-down transformer or low-voltage control circuit at the damper location.
FSLF24 US vs. FSLF120 US — Voltage Is the Only Difference
Both carry UL 555S listing. Both meet the same smoke damper actuator requirements. Use the one that matches your available supply voltage.
| Spec | HAC-90 (FSLF24 US) | HAC-80 (FSLF120 US) — this product |
|---|---|---|
| Supply Voltage | 24 Vac/dc | 120 Vac (line voltage) |
| UL 555S Listing | Yes | Yes |
| Application | Smoke dampers, 24 Vac control | Smoke dampers, 120 Vac line-voltage control |
| Action Code Source | Fire protection engineer | Fire protection engineer |
| Sizes | 6"–20" | 6"–20" |
| Choose When | 24 Vac control available — preferred for BAS/fire alarm integration | Only line voltage available at damper location |
Smoke Control System Integration
The HAC-80 operates as part of the building smoke control system — not independently as an HVAC component.
The FSLF120 US actuator receives its fail-safe signal from the smoke control panel or fire alarm system, which initiates damper movement as part of the engineered smoke control sequence. The installation contractor coordinates with the fire protection engineer and fire alarm system installer on control wiring, fail-safe signal source, and commissioning verification.
Configuration Guide
Action code confirmed by fire protection engineer. End switch wiring per smoke control system design. Confirm pricing at 20" before ordering.
| Variant Code | Action | End Switch | Heat Bypass | Part Number Example (10") |
|---|---|---|---|---|
| OPO | Spring-open on power loss | No | No bypass | HAC-1080-OPO |
| OPO-H | Spring-open on power loss | No | 10% bypass | HAC-1080-OPO-H |
| SPO | Spring-open on power loss | Yes | No bypass | HAC-1080-SPO |
| SPO-H | Spring-open on power loss | Yes | 10% bypass | HAC-1080-SPO-H |
| OPC | Spring-close on power loss | No | No bypass | HAC-1080-OPC |
| OPC-H | Spring-close on power loss | No | 10% bypass | HAC-1080-OPC-H |
| SPC | Spring-close on power loss | Yes | No bypass | HAC-1080-SPC |
| SPC-H | Spring-close on power loss | Yes | 10% bypass | HAC-1080-SPC-H |
Key Specs
Common Questions from the Counter
Answers to what comes up most when specifying the HAC-80.