PRE-ENGINEERED DAMPER INTERLOCK · 24 MODELS · MILLIVOLT · 24 VAC · 110 VAC

ADP Interface Relay Adaptors

Every Hoyme damper installation needs an interlock circuit. The ADP series does that work in advance — each model is pre-engineered for a specific damper and appliance sequence, with matched relay ratings, wiring logic, and color diagrams in every box.

Interlock handled by a BAS or DDC controller? Wire the damper end switch directly to the controller input — the ADP is for non-BAS residential and light commercial installations.

24 models — combustion air, fresh air, gas dryer, exhaust fan, and general purpose
Color wiring diagrams included in every box
Relays field-replaceable — no full unit replacement
A/C circuit unaffected on all models
ADP Interface Relay Adaptor

WHY IT MATTERS

What Happens Without Proper Interlock

A combustion air damper that is not interlocked with the appliance it serves is a code violation and a safety risk on every permitted residential and commercial job in Canada and the U.S.

Mechanical room showing combustion air duct — Hoyme ADP interlock

Without interlock, the appliance fires regardless of damper position.

In a tight modern home, that means the appliance is operating under negative pressure, pulling air past backdraft hazards and potentially down unsealed chimneys and other appliance vents. Combustion quality drops, carbon monoxide production rises, and the risk of backdrafting combustion products into the living space increases with every firing cycle.

Appliance fires with damper closed — combustion air drawn from building infiltration
Negative building pressure — air pulled past backdraft hazards and unsealed chimneys
Faults are invisible — a frozen blade or wiring problem goes undetected until a service call
Code violation on every permitted residential and commercial installation in Canada and the U.S.

The ADP interlock sequence prevents this: the appliance cannot fire until the damper end switch confirms the combustion air path is open. If the damper fails to open — frozen blade, motor fault, wiring problem — the appliance stays off and the fault is detectable rather than invisible.

Pre-matched relay ratings

Getting relay coil selection wrong on a millivolt or 24 Vac safety circuit loads the circuit and causes nuisance lockouts or damage. The ADP is pre-matched to the system voltage — no relay selection required in the field.

Documented for inspection

A field-assembled relay circuit in a junction box does not satisfy the documentation requirement inspectors look for on permitted installations. The ADP enclosure and color wiring diagram do.

Field-replaceable relays

A relay failure does not require replacing the complete ADP assembly. Relays are field-replaceable — order the relay, swap it in place. Up to 4 relays in a single enclosure depending on model.

ADP SERIES vs. FIELD-ASSEMBLED RELAY CIRCUIT

Field-Assembled Relay Circuit

Relay coil must be matched to source voltage — easy to get wrong
Sequencing logic non-trivial to design correctly in the field
Junction box assembly does not satisfy inspector documentation requirement
No wiring diagram — next technician has to reverse-engineer the circuit

Hoyme ADP Series

Relay ratings pre-matched to system voltage — millivolt through 110 Vac
Interlock logic pre-engineered per application — follow the color diagram
Labeled enclosure and color wiring diagram satisfy inspection documentation
Color wiring diagram in every box — next technician has everything they need

MODEL SELECTOR

Find Your ADP Model

All 24 models across three voltage groups. Find your system voltage, then match your application — each row is a unique ADP model verified against installation instructions and the 2026 price list.

Application

Voltage

Order This

Key Detail

Millivolt · 24 Vac — 10 Models · $48–$284

Combustion Air Interlock

Gas furnace — combustion air

Standing pilot · thermopile or thermocouple safety system

Millivolt

250mVdc – 100Vdc

ADP-0MV2-S5A

2 relays + test/run switch. The only ADP model rated for millivolt safety circuits — standard 24 Vac models will not work on standing pilot systems.

Gas furnace — combustion air + HOM interlock

Electronic ignition · 24 Vac control circuit · 10A relay

24 Vac

ADP-0241-10A

Proves HOM damper open before furnace fires. 10A relay output. Handles complex sequences with ventilation switch, replacement air damper, and inlet fan simultaneously. Wiring diagrams #7A1, #8B1.

Two appliances sharing one combustion air damper

One HOM-SF1 damper interlocked to two separate 24Vac safety circuits

24 Vac

ADP-0243-S5A

3 relays (1 DPDT + 2 SPDT) + 2 test/run switches. One damper proves open before either or both appliances fire independently or together. A third appliance can be added by upgrading to an SF2 damper.

Fresh Air, Ventilation & Furnace Fan Sequencing

Fresh air damper + furnace fan sequencing

Most specified — ventilation code compliance

24 Vac

ADP-0241-05A

Opens HAC damper first, confirms position via end switch, then energizes furnace fan. Prevents cold air dump on ventilation calls. Required for fresh air code compliance. Diagrams #7, #7A, #8, #8A, #8B, #8C, #8D and more.

Exhaust fan switch → fresh air damper + furnace fan

Also used for steam humidifier interlock (diagram #6A9)

24 Vac

ADP-0242-05A

2 relays. Exhaust fan switch (or auxiliary relay contact) simultaneously opens fresh air damper and turns on furnace fan. Second relay also opens damper during furnace firing. Diagrams #6A9, #8A9, #8B7, #8B8.

Split receptacle — plug-in fan or damper controlled by furnace

Controlled 120Vac outlet + continuous outlet · 10A

24 Vac

RADP-0241-10A

SPDT 10A + DPDT 5A relays in parallel. Split receptacle controlled side activates during furnace call or when damper end switch closes. Use when plug-in booster fan or damper must activate on a 24Vac furnace signal. Diagrams #7B, #8A2.

Gas Dryer Interlock

Gas dryer interlock — damper proves open before dryer operates

Split receptacle — dryer plugs in directly · red indicator switch

24 Vac

RADP-0241-S10A

Manual red light on/off switch opens fresh air damper and proves its position before dryer can operate. Split duplex receptacle — dryer plugs into the GAS DRYER side. Includes 5 ft plug-in cord. Diagrams #8A3–8A8.

Gas dryer interlock — two dampers required

Combustion air + replacement air both must prove open for dryer

24 Vac

RADP-0242-S10A

Interlocks gas dryer to two separate dampers simultaneously — both must prove open before dryer can fire. Split receptacle included. Use when combustion air duct also supplies replacement air for the dryer. Diagrams #8B5, #8B6.

Zone Control & General Purpose

Two-zone furnace fan control

Two independent zone damper circuits — HAC or HAC-H

24 Vac

ADP-0244-05A

Manages furnace fan sequencing for two zone circuits where the thermostat or zone controller does not directly handle fan start/stop logic. Prevents fan running when neither zone is calling.

Manual on/off switch — damper and/or furnace fan control

CSA-approved enclosure · no relay logic

24 Vac

ADP-0240-1WS

On/off switch in CSA enclosure. Switch OFF cuts power to a PC damper — springs it open. Also connects to furnace G & R terminals for manual furnace fan control. No relay — direct switch circuit only.

110 Vac — 13 Models · $88–$289

Combustion Air Interlock

Boiler or tankless water heater — combustion air proving

Up to 5A appliance load

110 Vac

ADP-1102-S5A

Damper proves open before appliance fires. 5A relay. Confirm appliance load on the electrical specification label before selecting between S5A and 10A. Diagram #11B.

Boiler or tankless water heater — combustion air proving

Up to 10A appliance load — larger commercial-grade units

110 Vac

ADP-1102-10A

Same function as ADP-1102-S5A with 10A relay output. Use when the appliance electrical spec label shows a load above 5A.

Exhaust Fan + Fresh Air Damper + Furnace Fan

120Vac exhaust fan switch → fresh air damper + furnace fan

Most specified 110Vac ventilation adaptor

110 Vac

ADP-1101-05A

120Vac exhaust fan switch simultaneously opens fresh air damper and activates furnace fan — without proving or timer logic. Does not interfere with A/C or combustion air damper. Diagrams #5, #5A, #5B, #6, #6A, #6B and many more.

120Vac exhaust fan (controlled line available) → 24Vac damper + furnace fan

Damper also opens during furnace firing — two-wire parallel

110 Vac

ADP-1102-TWP

Use when controlled 120Vac line voltage is available at the adaptor location. Controlled exhaust fan signal opens 24Vac damper + furnace fan simultaneously. Second relay optionally opens damper during furnace firing. Diagrams #6A4, #6A5, #6C, #6C1, #8C5, #8C6.

Two-switch exhaust fan controller — designated ventilation switch

One switch: fan only · second switch: fan + furnace fan + damper

110 Vac

ADP-1101-10AV

Primary switch runs exhaust fan only. Designated ventilation switch runs the same exhaust fan simultaneously with furnace circulation fan and fresh air damper. Two 120Vac coil relays — 10A contacts.

End-Switch Proving — Damper Proves Open Before Exhaust Fan Starts

Damper proves open → THEN exhaust fan + furnace fan run

Damper does NOT open during furnace firing

110 Vac

ADP-1102-TPX

Exhaust fan switch opens 24Vac fresh air damper — end switch confirms blade open — THEN exhaust fan and furnace fan activate. Damper does not open during furnace firing. Use ADP-1103-TPX if furnace firing must also open damper. Diagrams #11, #12, #12B, #12B3, #12C, #12D.

Damper proves open → THEN exhaust fan + furnace fan run

Damper ALSO opens during furnace firing · 3 relays

110 Vac

ADP-1103-TPX

Same proving sequence as ADP-1102-TPX (damper end switch proves before exhaust fan starts) plus a third relay — damper also opens during the furnace firing cycle. 3 relays total. Diagrams #12B1, #12B2, #12B4.

Damper proves open → THEN plug-in exhaust fan + furnace fan run

Split receptacle for plug-in fan · damper does NOT open during furnace firing

110 Vac

RADP-1102-TPX

Same proving sequence as ADP-1102-TPX but exhaust fan is plug-in type via split duplex receptacle (LIVE / CONTROLLED sides). Manual switch or timer activates sequence. Diagram #12A.

Dual Exhaust Fan + Furnace Fan + Fresh Air Damper

Two 110Vac exhaust fans — non-concurrent · furnace fan + damper for either

Requires ADP-1101-05A or ADP-1102-TWP as companion adaptor

110 Vac

ADP-1101-10AS

Interlocks two fans to prevent concurrent operation — turning on one stops the other. Furnace circulation fan and fresh air damper activate for whichever fan is running. Must be wired with ADP-1101-05A or ADP-1102-TWP. Diagrams #5B2, #5B3, #6A7, #6A8.

Two exhaust fans (120Vac + 24Vac/dry contact) → furnace fan + damper

Damper does NOT open during furnace firing

110 Vac

ADP-1102-TW5

Controlled 120Vac signal from one fan OR 24Vac/dry contact signal from a second fan both trigger furnace fan and fresh air damper simultaneously. Damper does not open during furnace firing. Use ADP-1103-TW5 if furnace firing must also open damper. Diagram #8B9.

Two exhaust fans (120Vac + 24Vac/dry contact) → furnace fan + damper

Damper ALSO opens during furnace firing · 3 relays

110 Vac

ADP-1103-TW5

Same as ADP-1102-TW5 but adds a third relay — fresh air damper also opens during the furnace firing cycle. 3 relays total vs 2 in ADP-1102-TW5.

Timer-Based — 24hr Grasslin Interval Timer Included

Timer + manual switch → exhaust fan + furnace fan + fresh air damper

Damper does NOT open during furnace firing

110 Vac

TMADP-1102-TPX

24hr Grasslin interval timer and/or manual ventilation switch simultaneously starts exhaust fan, activates furnace fan, and opens fresh air damper. Damper does NOT open during furnace firing. See Grasslin Timer Centre Pin Settings guide for programming. Diagrams #9, #9A, #9A1, #9A2, #9B, #9B1.

Timer + manual switch → exhaust fan + furnace fan + fresh air damper

Damper ALSO opens during furnace firing · 3 relays

110 Vac

TMADP-1103-TWP

Same as TMADP-1102-TPX but adds a third relay — fresh air damper also opens during furnace firing cycle. 3 relays vs 2. Use when damper must respond to both the ventilation timer AND the furnace thermostat.

Timer + split receptacle → plug-in exhaust fan + furnace fan + fresh air damper

Manual override switch option · plug-in fan

110 Vac

TRADP-1102-TPX

Same timer function as TMADP-1102-TPX but exhaust fan is plug-in type via split duplex receptacle. Manual override switch can be added to bypass the timer. Damper does not open during furnace firing.

Transformer / Special — 1 Model · $173

Switchable 24Vac power supply — manual damper control on demand

Example: fireplace fresh air intake damper · manual fresh air on demand

120Vac plug-in

24Vac output (up to 20VA)

ADP-024T-S20VA

120Vac plug-in transformer with on/off switch on face. Provides switchable 24Vac power to any 24Vac motorized damper on demand (up to 20VA). No interlock logic — direct manual control only. Plug in, flip switch, damper opens.

The end switch on the damper is not optional on combustion air and fresh air proving applications.

The ADP interlock sequence relies on the end switch signal to confirm the blade has physically reached open position. Without it, the ADP has no position confirmation and the interlock cannot function. When ordering the HOM, specify the SO2 variant. When ordering the HAC, specify SPO or SPC. This is the most common installation error on ADP applications.

Not sure which model fits your system?

Call technical support with your appliance type, system voltage, and damper model — we'll confirm the right ADP before you order.

MODEL DETAILS

What Each Model Does — and Why It's Different

Each ADP model is engineered for a specific application. Selecting the wrong model for the system voltage will not function correctly and may damage the safety circuit.

Covering the nine primary decision points. For all 24 models including dual-fan, zone, and special adaptors, see the complete selector above.

ADP-0MV2-S5A Millivolt · Gas Furnace

Combustion Air Interlock for Standing Pilot Furnaces

Older gas furnaces with a standing pilot use a thermopile or thermocouple safety system that operates at millivolt voltage levels — 250mVdc to 100Vdc. That voltage is too low and carries too little current to drive a standard relay without loading the safety circuit and causing nuisance lockouts or damage.

The ADP-0MV2-S5A is designed specifically for this voltage range. Two relays handle the interlock logic: the first accepts the millivolt signal from the safety system, the second provides the 24 Vac output to the damper motor and the proved-open return signal. A test/run switch allows commissioning without cycling the appliance.

The only ADP model rated for millivolt safety circuits — 24 Vac models will not work
2 relays — millivolt input, 24 Vac damper output
Test/run switch — commission without cycling appliance
Pair with HOM SO2 — end switch required

Use when: the furnace has a standing pilot, thermopile, or thermocouple. If the furnace predates 24 Vac electronic ignition controls, this is the correct model.

ADP-0MV2-S5A millivolt combustion air relay adaptor
ADP-0241-10A 24 Vac furnace combustion air relay adaptor
ADP-0241-10A 24 Vac · Gas Furnace

Combustion Air Interlock for 24 Vac Furnaces

The standard combustion air interlock for modern gas furnaces with 24 Vac electronic ignition controls. The HOM damper proves open before the furnace is allowed to fire — satisfying CAN/CSA B149 interlock requirements. 10A relay output handles high-demand sequences including ventilation switch, replacement air damper, and inlet fan combinations.

24 Vac furnace system — electronic ignition controls
HOM damper proves open before furnace fires
10A relay output — handles complex multi-fan sequences
A/C circuit unaffected
Pair with HOM SO2 — end switch required

Use when: gas furnace with 24 Vac electronic ignition and a HOM combustion air damper. If the furnace has a standing pilot, use ADP-0MV2-S5A instead.

ADP-0241-05A Most Specified · 24 Vac

Fresh Air Damper + Furnace Fan — Ventilation Code Compliance

The most specified ADP model for 24 Vac fresh air ventilation code compliance. A single relay (DPDT, 24 Vac coil) activates when the ventilation switch or exhaust fan switch closes — simultaneously opening the 24 Vac HAC fresh air damper and turning on the furnace circulation fan. One switching action handles both functions together.

In the standard configuration, the fresh air damper does not open during furnace firing — ventilation calls only. With a Power Close damper and relay, the damper can optionally also open during furnace firing.

Single DPDT relay — damper and furnace fan activate simultaneously
24 Vac coil — controlled by 24 Vac ventilation switch or exhaust fan switch
Standard: damper does NOT open during furnace firing — ventilation calls only
Optional: PC damper with relay allows damper to also open during furnace firing
A/C circuit unaffected · Pair with HAC OPO or OPC

Need damper to prove open BEFORE the exhaust fan is allowed to start? That requires end-switch proving logic — use RADP-1102-TPX (plug-in fan) or ADP-1103-TPX (hardwired fan).

ADP-0241-05A fresh air damper furnace fan relay adaptor
ADP-1102 110 Vac boiler combustion air relay adaptor
ADP-1102-S5A + ADP-1102-10A 110 Vac · Boiler / Tankless

Combustion Air Interlock for Boilers and Tankless Water Heaters

Both models interlock the HOM combustion air damper with 110 Vac boiler or tankless water heater control circuits. The damper proves open before the appliance is allowed to fire. The only difference is relay output rating — confirmed by the appliance's electrical specification label.

ADP-1102-S5A

5A relay — most residential boilers and standard tankless water heaters

110 Vac · up to 5A load

ADP-1102-10A

10A relay — larger commercial-grade boilers and higher-load tankless units

110 Vac · up to 10A load

Confirm the appliance load rating before selecting. The correct relay rating is on the appliance's electrical specification label. Wrong relay output for the load can cause relay failure.

ADP-1101-05A Most Specified · 110 Vac

110 Vac Exhaust Fan → Fresh Air Damper + Furnace Fan

The 110 Vac equivalent of the ADP-0241-05A and the most specified 110 Vac ventilation adaptor. A single relay (DPDT, 120 Vac coil) activates when the 120 Vac exhaust fan switch closes — simultaneously opening the 24 Vac fresh air inlet damper and turning on the furnace circulation fan.

Designed specifically to not interfere with the combustion air damper circuit or the A/C circuit. The combustion air damper opens only when the furnace fires — the ADP-1101-05A ventilation circuit operates independently. In standard wiring, the fresh air damper does not open during furnace firing.

Single DPDT relay — 120 Vac coil, 24 Vac / 120 Vac contact points
120 Vac exhaust fan switch simultaneously opens fresh air damper + activates furnace fan
Does not interfere with combustion air damper or A/C circuit
Standard: fresh air damper does NOT open during furnace firing
Pair with HAC OPO or OPC · wiring diagrams #5 through #6A3 and more

Need damper to prove open before fan starts? Use RADP-1102-TPX or ADP-1103-TPX — the proving models. ADP-1101-05A is simultaneous operation only.

ADP-1101-05A

Confirm image CDN URL in
Shopify Admin → Settings → Files

RADP-1102-TPX · ADP-1103-TPX

Confirm image CDN URL in
Shopify Admin → Settings → Files

RADP-1102-TPX + ADP-1103-TPX 110 Vac · Proving Adaptors

Damper Proves Open Before Exhaust Fan Starts

Both models interlock the exhaust fan to a fresh air damper with end switch using a proving sequence: the ventilation switch opens the damper, the damper end switch must confirm the blade has physically reached its open position, and only then does the exhaust fan and furnace circulation fan activate. The ADP-1101-05A opens both simultaneously — these proving models hold the fan off until the damper confirms open.

RADP-1102-TPX

Plug-in exhaust fan via split duplex receptacle. Damper does NOT open during furnace firing. 2 relays (C120V DPDT + C24V SPDT 10A).

Diagram #12A · plug-in fan

ADP-1103-TPX

Hardwired fan. Damper ALSO opens during furnace firing. 3 relays (C120V DPDT + 2× C24V SPDT 10A).

Diagrams #12B1, #12B4 · hardwired fan

End switch on the damper is required. Without the end switch, the adaptor has no position confirmation signal and the proving sequence cannot function. Order HAC with SPO or SPC variant.

TMADP-1102-TPX 110 Vac · Timer

Automatic Timed Ventilation — Grasslin 24 Hr Timer

When a ventilation code requires automatic, scheduled ventilation without manual intervention, the TMADP-1102-TPX handles both the scheduling and the circuit control. The built-in Grasslin 24 hr interval timer activates the ventilation sequence at set intervals — simultaneously starting the principal exhaust fan, turning on the furnace circulation fan, and opening the fresh air inlet damper.

A central ventilation switch also provides manual override at any time. In the standard configuration, the fresh air damper does not open during furnace firing. The enclosure is larger than standard ADP models (8×4×2.5" vs 5×4×2.5") to accommodate the timer mechanism. Refer to the Grasslin Timer Centre Pin Settings guide for programming.

Built-in Grasslin 24 hr interval timer — 15-min increments per pin
Timer and/or manual switch: exhaust fan + furnace fan + fresh air damper simultaneously
2 relays — 120 Vac coil (fan circuit) + 24 Vac coil (damper + furnace fan)
Standard: fresh air damper does NOT open during furnace firing
Larger enclosure: 8×4×2.5" — plan mounting location accordingly

Use when: ventilation code requires automatic scheduled ventilation rather than occupant-controlled ventilation. If damper must also open during furnace firing, use TMADP-1103-TWP. Wiring diagrams #9, #9A, #9A1, #9A2, #9B, #9B1, #9C, #9C1, #10.

TMADP-1102-TPX

Confirm image CDN URL in
Shopify Admin → Settings → Files

RADP-0241-S10A gas dryer interlock relay adaptor with red indicator switch
RADP-0241-S10A 24 Vac · Gas Dryer

Gas Dryer Interlock with Red Indicator Switch

Gas dryers installed with a motorized fresh air or combustion air damper need an interlock — the dryer cannot operate until the damper proves open. The RADP-0241-S10A includes a manual red light on/off switch: turning it on opens the damper and proves its position, then the dryer receptacle becomes live. Visual confirmation the circuit is active is provided by the indicator light remaining on while the dryer runs.

The dryer plugs directly into the GAS DRYER side of the split duplex receptacle — no hardwiring of the dryer connection required. The included 5 ft plug-in cord mounts near the dryer for easy switch access.

Manual red indicator switch — proves damper open before dryer can operate
Split duplex receptacle — dryer plugs into GAS DRYER side directly
5 ft plug-in cord included — mounts near dryer for easy operation
24 Vac — standard residential gas dryer installations
Pair with HOM SO2, HAC SPO/SPC, or BDH with end switch

110 Vac gas dryer applications: contact factory. The current product lineup does not include a direct 110 Vac equivalent with the same red indicator proving circuit.

ADP-0244-05A two-zone furnace fan control relay adaptor
ADP-0244-05A 24 Vac · Two-Zone

Two-Zone Furnace Fan Control

On two-zone systems with independent zone damper circuits, the furnace fan must respond correctly to zone calls from both circuits. Where the thermostat or zone controller does not directly manage fan sequencing, the ADP-0244-05A coordinates fan operation — preventing the fan from running when neither zone is calling and handling correct fan start/stop logic when one or both zones are active.

Two independent zone circuits — HAC or HAC-H dampers
Fan runs only when at least one zone is calling
Correct start/stop logic when one or both zones are active
24 Vac — confirm end switch requirement with wiring diagram

Use when: two-zone HAC or HAC-H system where the thermostat or zone controller does not directly manage furnace fan sequencing for both zones.

BEFORE YOU ORDER

The End Switch on the Damper Is Not Optional

Several ADP models rely on the end switch signal from the damper to complete the interlock sequence. Without it, those models have no position confirmation and the interlock cannot function. This is the most common installation error on ADP applications.

What the end switch does — and which models need it

A motor receiving 24 Vac does not confirm the blade has actually moved. The end switch is a physical microswitch mounted on the damper body that closes when the blade reaches its open position — providing the proved-open signal that confirms the damper has physically arrived at open, not just that power was applied.

Proving models — those with "TPX" in the model number and the RADP-0241-S10A — use this signal to hold the appliance or exhaust fan off until proved-open is received. Simultaneous models (ADP-0241-05A, ADP-1101-05A) activate all outputs at once and do not require an end switch. The compatibility table below shows which applies to each model.

On proving models — what goes wrong without end switch:

ADP has no position confirmation signal — interlock sequence cannot complete
Appliance may fire regardless of damper position — code violation and safety risk
Frozen blade or motor fault goes undetected — fault is invisible, not detectable
Installation does not satisfy CAN/CSA B149 interlock requirements

Order the damper with end switch — where required:

HOM

Specify SO2 variant

Spring Open, relay included, end switch included — required for ADP-0MV2-S5A, ADP-0241-10A, ADP-1102-S5A, ADP-1102-10A combustion air interlock sequences

HAC

Specify SPO or SPC variant — for proving models only

S prefix = end switch included — required for RADP-1102-TPX and ADP-1103-TPX proving sequences. ADP-0241-05A and ADP-1101-05A use OPO or OPC (no end switch).

BDH

Order with end switch option

Required for RADP-0241-S10A gas dryer interlock proving circuit

Hoyme HAC inline damper with end switch — SPO variant

The end switch — what to order

The HAC damper shown here is the SPO variant — S prefix confirms end switch included. When the blade reaches fully open, the switch closes and sends the proved-open signal to the ADP relay adaptor. Order HAC with S prefix for proving model applications, or HOM SO2 for combustion air applications. For ADP-0241-05A and ADP-1101-05A (simultaneous models), use OPO or OPC — no end switch needed.

ADP Model

Damper to Order

End Switch Required?

Combustion Air Proving — End Switch Required

ADP-0MV2-S5A

HOM with end switch — SO2 variant

Yes — order HOM SO2
ADP-0241-10A

HOM with end switch — SO2 variant

Yes — order HOM SO2
ADP-1102-S5A ADP-1102-10A

HOM with end switch — SO2 variant

Yes — order HOM SO2

End-Switch Proving — End Switch Required

RADP-1102-TPX ADP-1103-TPX

HAC with end switch — SPO or SPC variant

Yes — order HAC SPO or SPC

Gas Dryer Interlock — End Switch Required

RADP-0241-S10A

BDH with end switch or HAC with end switch — SPO or SPC variant

Yes — proving circuit requires end switch

Simultaneous Operation — End Switch Not Required

ADP-0241-05A

HAC — OPO or OPC variant (no end switch)

No — simultaneous operation
ADP-1101-05A

HAC — OPO or OPC variant (no end switch)

No — simultaneous operation

Zone Control

ADP-0244-05A

HAC or HAC-H — zone dampers

Confirm with wiring diagram

SHOP ADP SERIES

Order the Right ADP Model

All 24 models ship from the same product page — select your model at checkout. The 8 primary models are shown below. For all 24 models including timer, dual-fan, and proving adaptors, see the complete selector above.

Hoyme ADP Interface Relay Adaptors

ADP Interface Relay Adaptors — 24 Models

ADP-0MV2-S5A · ADP-0241-10A · ADP-0241-05A · ADP-1102-S5A · ADP-1102-10A · ADP-1101-05A · RADP-0241-S10A · ADP-0244-05A · and 16 more — select at checkout

Shop ADP Series →

QUICK REFERENCE — PRIMARY MODELS BY APPLICATION

ADP-0MV2-S5A
ADP-0MV2-S5A

Gas furnace — millivolt

Standing pilot · thermopile/thermocouple · only model rated for millivolt safety circuits

ADP-0241-10A
ADP-0241-10A

Gas furnace — 24 Vac combustion air

Electronic ignition · HOM damper proves open before furnace fires · 10A relay output

ADP-0241-05A
ADP-0241-05A Most Specified

Fresh air damper + furnace fan — 24 Vac

Ventilation switch simultaneously opens HAC fresh air damper and activates furnace fan · standard ventilation code model

ADP-1102-S5A
ADP-1102-S5A

Boiler / tankless — 110 Vac · up to 5A

Most residential boilers and standard tankless water heaters · confirm load rating before ordering

ADP-1102-10A
ADP-1102-10A

Boiler / tankless — 110 Vac · up to 10A

Larger commercial-grade boilers and tankless units · confirm load rating on appliance spec label

IMG
ADP-1101-05A Most Specified

Fresh air damper + furnace fan — 110 Vac

120 Vac exhaust fan switch simultaneously opens fresh air damper and activates furnace fan · most specified 110 Vac ventilation adaptor

RADP-0241-S10A
RADP-0241-S10A

Gas dryer interlock — 24 Vac

Red indicator switch proves damper open before dryer operates · split receptacle · dryer plugs in directly · 5 ft cord included

ADP-0244-05A
ADP-0244-05A

Two-zone furnace fan control — 24 Vac

Two independent zone circuits · HAC or HAC-H · where zone controller doesn't manage fan sequencing

COMPANION DAMPERS — WHAT TO ORDER

Not sure which ADP model fits your system?

Call technical support with your appliance type, system voltage, and damper model — we'll confirm the correct ADP and damper variant before you order.

COMMON QUESTIONS

ADP Relay Adaptor FAQs

Questions contractors and counter staff ask most often — answered directly from the product.

Why use an ADP instead of sourcing relays separately? +

Three reasons.

1

Relay coil matching

Relay selection for a millivolt or 24 Vac safety circuit requires matching the relay coil to the source voltage and current. Getting this wrong loads the safety circuit and causes nuisance lockouts or damage. The ADP is pre-matched — no selection required.

2

Interlock logic pre-engineered per application

On proving and timer models — such as RADP-1102-TPX, ADP-1103-TPX, and TMADP-1102-TPX — the relay logic requires timing and multi-relay sequencing that is non-trivial to design and wire correctly in the field. The ADP has this pre-engineered for the specific application. Follow the color wiring diagram in the box.

3

Inspection documentation

The ADP enclosure and color wiring diagram satisfy the documentation requirement that inspectors look for on permitted installations. A field-assembled relay circuit in a junction box does not.

My furnace has a standing pilot and thermopile. Which ADP do I need? +

ADP-0MV2-S5A. Standing pilot furnaces with thermopile or thermocouple safety systems operate at millivolt voltage levels — 250mVdc to 100Vdc. The standard 24 Vac ADP models will not work on these systems and must not be used.

The ADP-0MV2-S5A is the only model in the ADP series rated for millivolt safety circuits. It uses two relays — the first accepts the millivolt signal from the safety system, the second provides the 24 Vac output to the damper motor. A test/run switch allows commissioning without cycling the appliance.

⚠ If you are unsure whether the furnace uses millivolt or 24 Vac controls, check the furnace nameplate or call technical support before ordering — using the wrong model on a millivolt safety circuit can damage the safety system.

Do I need the end switch on the damper when using an ADP? +

It depends on the ADP model. Combustion air proving models and end-switch proving models require the end switch — they use the proved-open signal to hold the appliance or exhaust fan off until the damper confirms it has physically reached the open position. Simultaneous models activate all outputs at once and do not require an end switch.

End switch required — HOM SO2

ADP-0MV2-S5A, ADP-0241-10A, ADP-1102-S5A, ADP-1102-10A — combustion air proving models. Order HOM SO2 variant.

End switch required — HAC SPO or SPC

RADP-1102-TPX, ADP-1103-TPX — end-switch proving models. Order HAC SPO or SPC variant. S prefix = end switch included.

No end switch required — HAC OPO or OPC

ADP-0241-05A, ADP-1101-05A — simultaneous models. Order HAC OPO or OPC variant. O prefix = no end switch.

Ordering the wrong damper variant — end switch when not needed, or no end switch when required — is the most common installation error on ADP applications. Confirm your ADP model against the compatibility table above before ordering the companion damper.

Will the ADP affect the air conditioning circuit? +

No. All ADP models are designed so that the relay logic does not affect the A/C circuit. This is a specific design requirement for all models and is documented in the wiring diagram included in the box. The A/C system operates independently of the damper interlock circuit on all ADP installations.

Confirm A/C wiring is routed separately from the interlock circuit as shown in the color wiring diagram.

What's the difference between ADP-1102-S5A and ADP-1102-10A? +

Both models are for 110 Vac combustion air interlock on boilers and tankless water heaters. The only difference is the relay output rating.

ADP-1102-S5A — 5A output

Suitable for most residential boilers and standard residential tankless water heaters.

ADP-1102-10A — 10A output

Larger commercial-grade boilers and tankless units with higher electrical load at the appliance safety circuit.

Confirm the appliance load rating before selecting. The correct relay rating is on the appliance's electrical specification label. Using the wrong relay output for the load can cause relay failure.

Is the ADP required by code? +

The interlock between a combustion air damper and the appliance it serves is required by code on permitted residential and commercial installations in Canada and the U.S. The ADP itself is not the only way to achieve that interlock — a BAS relay output or a custom relay circuit can also satisfy the requirement.

The ADP is the pre-engineered solution that satisfies the requirement with documented wiring, matched relay ratings, and a form that inspectors recognize. On non-BAS residential and light commercial installations, the ADP is the practical standard.

Can the ADP be used with a Belimo actuator HAC damper? +

Yes. The ADP end switch input accepts the standard Hoyme end switch signal output. Belimo actuator HAC models — HAC-40, HAC-43, HAC-34, and others — have the same end switch option as the standard HAC family. If the Belimo actuator HAC is ordered with the end switch option, the end switch output is compatible with ADP input circuits.

Confirm wiring with the color wiring diagram for the specific ADP model before connecting.

What's in the box? What do I need to supply? +

In the box:

ADP relay adaptor enclosure — relays installed and pre-wired for the model ordered
Color wiring diagram specific to the model
Installation instructions

You supply:

All field wiring between ADP, damper end switch (if required), damper motor, and appliance safety circuit
Wire gauge and routing per local electrical code
Companion damper — variant depends on model:
Combustion air models: HOM SO2
Proving models (TPX): HAC SPO or SPC
Simultaneous models (ADP-0241-05A, ADP-1101-05A): HAC OPO or OPC
Who do I call if I'm unsure which model to order? +

Call Hoyme technical support directly. Have your appliance type, system voltage, and damper model ready — the call is typically under five minutes and we'll confirm the right ADP model, end switch variant, and wiring approach before you order.

READY TO ORDER

The Right ADP. Right Damper. First Time.

Confirm your ADP model and end switch variant before ordering — call technical support with your appliance type and system voltage.

24 models — combustion air, fresh air, gas dryer, zone control Colour wiring diagrams in every box Pre-matched relay ratings — millivolt through 110 Vac Relays field-replaceable — no full unit replacement In stock at Canadian HVAC wholesalers