Colored Wiring Diagram #9A4

120Vac Vent Fans, Vent Switch, Timer Adaptor with 1102-TWP Adaptor, Replacement air damper (Power Open)

HMI Hoyme Manufacturing Inc. Special Note: Circuits are colored for clarification only and are not necessarily those found in actual installations

Color Wiring Diagram #9A4

Diagram #9A4: Forced Air Furnace having a replacement air supply duct together with two (or more) exhaust fans controlled by two (or more) separate Double Pole Ventilation Switches, a Timer Adaptor and an Adaptor controlled by the Thermostat.

1. Replacement Air Damper (HAC-0x10-OPO) to control fresh air inlet; 
2. Controlled 120Vac(3-Wires) from the main exhaust fan and controlled 120Vac (2-wire) from additional exhaust fans are required to the furnace area; 
3. Double Pole Ventilation Switches for two or more exhaust fans; 
4. Relay Adaptor with Interval Timer (TMADP-1102-TPX) functions as the automatic control center together with Relay Adaptor (ADP-1102-TWP) allowing for additional exhaust fans to be added and also the thermostat to be interconnected.

OPERATION: 
1. Fresh air damper opens during Furnace firing. 
2. Ventilation Switch from any area and/or bathroom timer turns on Exhaust Fan opens Replacement Air Damper and turns on Furnace Fan simultaneously. 
3. Adaptor Interval Timer can be set for minimum or multiple consecutive settings of 15 minutes to simultaneously turn on the principal Ventilation Fan open Replacement Air Damper and turn on the Furnace Fan
4. Optional switch connected between terminals #1 and #2 of the Adaptors allows full control of the Power Open Replacement Air Damper to open as required.

(When using a Power Close Damper, refer to Diagram #9A5)
Note: Power supply shall be from one circuit.

N.B. Replacement Air Damper is not affected by the ‘Manual’ setting of the furnace fan.