Colored Wiring Diagram #8C6

Two Forced Air Furnaces sharing a replacement air supply duct controlled by one fresh air damper with Power Close Damper
HMI Hoyme Manufacturing Inc. Special Note: Circuits are colored for clarification only and are not necessarily those found in actual installations.
Diagram #8C6: Two Forced Air Furnaces sharing a common replacement air supply duct equipped with one Power Close fresh air damper. A designated ventilation switch and/or bathroom timer interconnected to an ADP-1102-TWP acting as a control centre for one furnace and an ADP-0241-05A interconnected and acting as a control centre for the other furnace.
 
1. Replacement Air Control Damper, Power Close (HAC-0x10-OPC) where ‘x’ = diameter of the damper. (Note: If using a Power Open damper, go to wiring Diagram #8C5 for details.) 
2. Ventilation switch and/or bathroom timer. 
3. 24Vac Relay Adaptors (ADP-1102-TWP) and (ADP-0241-05A).

OPERATION:
1. Damper opens when either furnace fires. 
2. The ventilation switch simultaneously turns on the exhaust fan, opens the damper and turns on the circulation fan on one furnace only. 
3. Optional Switch allows full control of Replacement Air damper to open as required.

N.B. Replacement Air Damper is not affected by the ‘Manual’ setting of the furnace fan or by the operation of an Air Conditioner.