Home

Colored Wiring Diagram #3A1

Combustion air damper and replacement air damper (Power Open) & Optional switch
 
HMI Hoyme Manufacturing Inc. Special Note: Circuits are colored for clarification only and are not necessarily those found in actual installations.  Combustion Air Damper Wires, however, are colored as shown.
Diagram #3A1: Forced Air Furnace having a fresh air supply duct for combustion and a replacement air supply duct leading to the return plenum.
 
ADDED:  
1. Combustion Air Damper (HOM-0x11-SF1) 
2. Replacement Air Damper. (Power Open) (HAC-0x10-OPO)
3. Optional SPDT Toggle Switch.
 
OPERATION:  
1. Combustion Air Damper is interlocked to the thermostat so that the damper proves to be open to supply fresh air for combustion before the furnace fires. The damper closes to conserve energy when the fire stops.
2. Replacement Air Damper is interconnected to the thermostat so that the damper opens to provide fresh air into the return plenum only during the heating cycle and will close to provide comfort and conserve energy when the fire stops. Heat Anticipator adjustment may be required on a regular type thermostat. The damper will also remain closed during furnace fan operation.
3. To override the normally closed damper, use an optional SPDT Toggle   Switch as shown. For ease of installation, consider a Hoyme ready mounted optional switch   ADP-0240-3WS shown in Diagram #3A2 .

N.B. Replacement Air Damper is not affected by the ‘Manual’ setting of the furnace fan .

1222-ld - Printed in Canada

Printer friendly (pdf)     - (Opens in a new window)

Last Updated (Tuesday, 09 August 2016 09:35)